SEER2 energy savings calculator and customer report
Free from Relay, no signup. Defaults and sources checked November 13, 2026.
Compare two cooling systems serving the same seasonal cooling load. Enter equivalent full-load cooling hours, not total compressor run hours. Both ratings must be SEER2.
Method
Seasonal cooling energy (kWh) = cooling capacity (Btu/h) × equivalent full-load hours ÷ (SEER2 × 1,000). Annual cost = kWh × electricity rate. Simple payback = additional upgrade cost ÷ positive annual savings.
Worked example
At 36,000 Btu/h and 1,200 equivalent full-load hours, 14 SEER2 uses about 3,086 kWh and 18 SEER2 uses 2,400 kWh. At $0.16/kWh, the difference is about $110 a year. A $1,500 upgrade premium has a simple payback of about 13.7 years.
What this calculation covers
A seasonal scenario, not a bill forecast, sizing recommendation or guaranteed saving. No fixed conversion between SEER and SEER2 is applied. Weather, duct losses, installation, controls, heating, rate tiers and future prices are excluded. Use matched equipment ratings; do not compare SEER with SEER2.
Method references
Continue your work
Questions
Can I share the calculation with a customer?
Yes. Calculate, open Prepare a report, optionally add a customer or project name, and download a PDF with your inputs, method, references and limitations. Inputs stay in your browser.