Hydronic water flow and heat transfer calculator
Free from Relay, no signup. Defaults and sources checked November 13, 2026.
Estimate sensible heat transfer in a plain-water loop. Start with measured flow and temperature difference, or a known heat load. This is an initial estimate using fixed water properties.
Method
For a plain-water initial estimate: heat (Btu/h) = approximately 500 × US gallons/min × temperature difference (°F). In metric units: heat (kW) = approximately 4.180741 × L/s × temperature difference (°C). Solve the same equation for flow when the heat load is known.
Worked example
At 6 US gpm and a 20°F supply-return difference, heat transfer is approximately 60,000 Btu/h. A 60,000 Btu/h load at a 20°F difference needs approximately 6 US gpm under these assumptions.
What this calculation covers
Plain water only. Fixed density and specific heat are approximate and temperature-dependent; the 500 factor is rounded. Do not use this shortcut for glycol, refrigerant, steam, pump selection, pipe sizing or final system design. A zero temperature difference cannot determine flow for a load.
Method references
Continue your work
Questions
Can I share the calculation with a customer?
Yes. Calculate, open Prepare a report, optionally add a customer or project name, and download a PDF with your inputs, method, references and limitations. Inputs stay in your browser.