Duct velocity calculator for round and rectangular ducts
Free from Relay, no signup. Defaults and sources checked November 13, 2026.
Calculate average air velocity for a known flow and clear internal duct area. Use the dimensions inside any lining, not the outside sheet-metal dimensions.
Method
Average velocity = volume flow ÷ cross-sectional area. Round area = π × diameter² ÷ 4. Rectangular area = width × height. Divide square inches by 144 for ft²; divide square millimeters by 1,000,000 for m² and L/s by 1,000 for m³/s.
Worked example
400 CFM through a 12-inch round duct has an average velocity of about 509 ft/min. The same flow in a clear 12 × 8-inch rectangle has a velocity of 600 ft/min.
What this calculation covers
This is a velocity worksheet, not a duct sizing or Manual D calculator. It does not account for friction, fittings, flex compression, leakage, available static pressure, noise or fan performance. A single centerline reading is not the cross-sectional average.
Method references
Continue your work
Questions
Can I share the calculation with a customer?
Yes. Calculate, open Prepare a report, optionally add a customer or project name, and download a PDF with your inputs, method, references and limitations. Inputs stay in your browser.